This study investigate heat release rate of cables and wires used on constructions. The short circuit of cable or wires is one of the major reasons which cause fires, and injury comes from high temperatures, high heat fluxes, and large amounts of toxic gases being emitted. Therefore, the heat release rate of material pre- sents the parameters of reaction to fire. The apparatus of heat release rate test are Cone Calorimeter and Factory Mutual Calorimeter, which are bench- scale. It based on the principle of oxygen consumption to measure heat release rate. The testing sample used were cables and wires according to National stan- dards for construction. The results showed that the cable of CNS 11359 would not be burned within 20 minutes under the heat which are 14 kw/m2, the rest of peak of heat release rate greater than 12.5 kw/m2, which needed for burning of wooden materials. It could burn the adjoin- ing combustibles .It was also simultaneously found that the curve of heat release rate for Cone calorimeter are similar to Factory Mutual Calorimeter, and the relationship for total heat release rate between Cone calorimeter and Factory Mutual Calorimeter are close to linear.
|