The purpose of this thesis is to investigate the proper installation location of strong motion seismometers for various structure systems. The procedure includes following main steps: Step 1 : determining the natural frequencies and their corresponding modal shapes Step 2 : determining the major contribution modes to the earthquake response in X direction and Y direction Step 3 : deciding the proper location on horizontal plane Step 3 : deciding the proper location on vertical plane In step 2, 3, 4 the 1940 El Centro earthquake is used to calculated the earthquake response. According to the analysis executed, it is concluded that: 1. For complicated structure system, the influence of tortional mode will be more visible. 2. For structure system with L-shape plane, the long wing will influence the channel parallel to the short wing. 3. Non-symmetrical Wall system has visible influence on the location of seismometers, specially on the channel parallel to the wall plane. 4. The influence due to the flexure rigitity of slab and the strong-stiffness-story are not very visible in the cases investigated. 5. In Ming-Li Elementary School Building and the Administration Building of Cheng-Kung University, some of the seismometers installed need to be adjusted.
|